Local Control Panel (LCP) is designed for controlling the emergency isolation valve (ESD or ESV) locally nearby the valve via Neles ValvGuard VG9000 intelligent solenoid valve.
LCP permits the emergency isolation valve to be closed (or opened) locally and permits the valve to be returned to the normal operating position when the trip initiators are normal (Manual Reset - function).
There is also functional testing (Partial Stroke Testing, PST) possibility of the emergency isolation valve.
Indicators (LED's) for the valve position (open/ close), ready to reset, testing and alarm status are included too.
Communication between the LCP and VG9000 is handled by a current loop.
LCP has two options for the supply power; external 24 Vdc or loop-powered. In the loop power version the supply power is taken from the input loop for VG9000H.
ATEX - Intrinsically Safe: Ex ia IIC T6-T4 Gb, Ex Ic IIC T6-T4 Gc, Ex Eb Mb (Ib) IIC T6-T4 Gb, Flameproof & Explosion-proof: Exd IIB+H² T6 Gb, Ex Tb IIIC T85° C Db
IECEx - Intrinsically Safe: Ex ia IIC T6-T4 Gb, Ex Ic IIC T6-T4 Gc, Ex Eb Mb (Ib) IIC T6-T4 Gb, Flameproof & Explosion-proof: Exd IIB+H² T6 Gb, Ex Tb IIIC T85° C Db
INMETRO - Intrinsically Safe: Ex ia IIC T6-T4 Gb, Ex Ic IIC T6-T4 Gc, Flameproof & Explosion-proof: Ex d IIB+H² T6 Gb, Ex Tb IIIC T85° C Db
Communication
HART
Electrical Contacts
Normally Open
Enclosure, Body Material
316L Stainless Steel
Aluminum Alloy
Environmental Protection
IP66
Function
Manual Reset
Indication
LED
Power Supply
Externally Powered (Min.): 11 Vdc / 50 mA
Externally Powered: 24 Vdc / 50 mA
Temperature Range
-20° to 65° C (-4° to 149° F) - Ex d & Ex E Version