IM Series Interface Module
Brand: Turck, IncTURCK's IM series of Isolating Intrinsically Safe Barriers is designed to be a simple and safe way to solve the
problems associated with the installation of equipment that is used in potentially explosive atmospheres.
TURCK's IM series uses the intrinsically safe concept that is universally accepted, easy to apply and the safest
way to install electronic measuring, monitoring and control equipment in potentially explosive atmospheres.
The IM series uses state-of-the-art circuitry and the latest technology to produce a product that
provides the best explosion protection interfaces on the market.
The IM series of Intrinsically Safe Interface Devices is application specific: Each device is designed to work in a
specific application, be it analog input, analog output, discrete input, discrete output or others.
TURCK designed the IM series to handle most applications where instrumentation and controls are typically installed in potentially explosive
atmospheres, reducing the number of model variations of spares consolidates stocking requirments and making inventory control simpler.
Intrinsic safety has come of age with the introduction of the IM series of Intrinsically Safe Isolating Barriers, making
IS applications in potentially explosive atmospheres safe, simple and economically attractive.
- Input: 1, 2, or 4 Channel
- Output: 1, 2 or 5 Non-Hazardous Switching Circuits, 0-20 mA
- Alarm: Non-Hazardous SPST Switch for open or short circuits
- Pin Configuration: 18 mm, 12-pin or 27 mm, 20-pin Connectors
- Housing: Polycarbonate/ABS
- Temperature Ranges
- Operating: -25° to +60° C (-13° to +140° F)
- Storage: -40° to +80° C (-40° to +176° F)
- Operating Voltage: 20-125 Vdc (20-250 Vac) or 24 Vdc (ranges 10-30 Vdc)
- Options
- Relay or Transistor Output Switch
- Voltage or Current Output
- HART Compatibility
- Loop Powered Input
- Software Configurable with PC for Temperature Relay
- Configurable Limit Value Relay Output
- Mounting: DIN Rail or Panel
- Protection: IP20
- Intrinsically Safe
Displaying prices & availability for Ohio, United States in CAD. Change location.
- Featured
- Quantity In Stock
- Price
- SKU / Model Number
- IM: Interface Module
- 33: Analog Input Repeaters/Supplies
- 2: Number of Hazardous Area Inputs
- 2: Number of Non-Hazardous Area Outputs
- EX: Intrinsically Safe Associated Apparatus
- HI: HART Compatible
- 24VDC: Supply Voltage (19-29 VDC)
- ATEX, IECEx, UL, cFMus, TR CU, TIIS, CCOE, Kosha
- Installation in Zone 2
- Supply of 2-wire measuring transducers with HART communication as well as connection to active 2-wire and passive 3-wire transmitters
- Input Circuits: 0/4...20mA
- Output Circuits: 0/4...20mA
- SIL2
- Removable terminal blocks, screwable with 2mm test socket
- Complete galvanic isolation
- Output: (1) Transistor, Digital, Single or Parallel Operation
- Output Range: 24-28 VDC, 2.5 A Nominal Current
- Electrical Connection: Screw Terminals
- Housing: Polycarbonate/ABS
- Temperature Ranges:
- Operating: -25°C to +70°C (-13°F to +158°F)
- Storage: -40°C to +85°C (-40°F to +185°F)
- Function: Power Supply for DC Loads, Switching & Monitoring of TURCK Interface Modules
- Protection: [/b]IP20
- Intrinsically Safe
- IM: Interface Module
- 1: Isolation Switch Relay
- 1: Number of Inputs
- 2: Number of Non-Hazardous Area Outputs, Reflecting Hazardous Area Input Status
- EX: Intrinsically Safe Associated Apparatus
- R: Relay Switch
- IM: Interface Module
- 33: Analog Input Repeaters/Supplies
- 1: Number of Hazardous Area Inputs
- 2: Number of Non-Hazardous Area Outputs
- EX: Intrinsically Safe Associated Apparatus
- HI: HART Compatible
- 24VDC: Supply Voltage (19-29 VDC)
- IM: Interface Module
- 1: Isolation Switch Relay
- 1: Number of Inputs
- 2: Number of Non-Hazardous Area Outputs, Reflecting Hazardous Area Input Status
- 1: Number of Additional Non-Hazardous Area Alarm Outputs
- EX: Intrinsically Safe Associated Apparatus
- R: Relay Switch
- IM: Interface Module
- 72: Solenoid Driver/Discrete Output Isolators
- 2: Number of Hazardous Area Inputs
- 2: Number of Non-Hazardous Area Current Output Channels
- EX: Intrinsically Safe Associated Apparatus
- L: Loop Power
- IM: Interface Module
- 1: Isolation Switch Relay
- 1: Number of Inputs
- 2: Number of Non-Hazardous Area Outputs, Reflecting Hazardous Area Input Status
- EX: Intrinsically Safe Associated Apparatus
- T: Transistor Switch
- Output: (1) Transistor, Digital, Single or Parallel Operation
- Output Range: 22.5-28.5 VDC, 5.0 A Nominal Current
- Electrical Connection: Screw Terminals
- Housing: Polycarbonate/ABS
- Temperature Ranges:
- Operating: -25°C to +70°C (-13°F to +158°F)
- Storage: -40°C to +85°C (-40°F to +185°F)
- Function: Power Supply for DC Loads, Switching & Monitoring of TURCK Interface Modules
- Protection: [/b]IP20
- Class 1 Div 2
- ATEX, IECEx
- Zone 2
- Collective fault signal via relay
- Single and reundant power supply via terminals
- Supply inputs are decoupled
- Reverse Polarity protection
- Removable screw terminals
- Protection Class: IP20
- Nominal voltage: 24 VDC / 7A
- Operating voltage: 11...30 VDC
- IM: Interface Module
- 1: Isolation Switch Relay
- 4: Number of Inputs
- 5: Number of Non-Hazardous Area Outputs, Reflecting Hazardous Area Input Status
- 1: Number of Additional Non-Hazardous Area Alarm Outputs
- EX: Intrinsically Safe Associated Apparatus
- R: Relay Switch
- IM: Interface Module
- 33: Analog Input Repeaters/Supplies
- 1: Number of Hazardous Area Inputs
- 1: Number of Non-Hazardous Area Outputs
- EX: Intrinsically Safe Associated Apparatus
- HI: HART Compatible
- 24VDC: Supply Voltage (19-29 VDC)
- Function: Temperature Converter
- Input: 1 Hazardous Area Channel
- Output: 2 Non-Hazardous Area Channels
- Signal: RTD, T/C, or mV into 4/20 mA
- Configuration: Software Configurable
- Supply Voltage: 20-250 VAC or 20-125 VDC
- Temperature Range:
- Operating: -25°C to +60°C (-13°F to +140°F)
- Storage: -40°C to +80°C (-40°F to +176°F)
- Intriniscally Safe Associated Apparatus
- ATEX, IECEx
- Zone 2
- SIL 2
- Input circuits monitored for wire-break and short-circuit
- Parametrized via PC
- Complete galvanic isolation
- Removable screw terminals
- Protection Class: IP20
- Nominal voltage: 24 VDC / 7A
- Operating voltage: 11…30 VDC
- Input: 1 Channel 4-20mA or 2-10VDC
- Output: 3(x) Relay Circuits, Digital
- Electrical Connection: 4 x 5-pole removable terminal block screw connection
- Housing: Polycarbonate/ABS
- Temperature Ranges:
- Operating: -25°C to +70°C (-13°F to +158°F)
- Storage: -40°C to +80°C (-40°F to +176°F)
- Operating Voltage: 20-250 VDC
- Function: Limit Value Indicator, 1 Input, 3 Limit Values
- Adjustment: limit value relay via rotary coding switches, hysteresis and signal flow via DIP switch
- Protection: [/b]IP20
- Intrinsically Safe
- IM: Interface Module
- 1: Isolation Switch Relay
- 2: Number of Inputs
- 2: Number of Non-Hazardous Area Outputs, Reflecting Hazardous Area Input Status
- EX: Intrinsically Safe Associated Apparatus
- R: Relay Switch
- IM: Interface Module
- 33: Analog Input Repeaters/Supplies
- 1: Number of Hazardous Area Inputs
- 2: Number of Non-Hazardous Area Outputs
- EX: Intrinsically Safe Associated Apparatus
- HI: HART Compatible
- Output: (1) Transistor, Digital, Single or Parallel Operation
- Output Range: 22.5-28.5 VDC, 5.0 A Nominal Current
- Electrical Connection: Screw Terminals
- Housing: Metal
- Temperature Ranges:
- Operating: -25°C to +70°C (-13°F to +158°F)
- Storage: -25°C to +85°C (-13°F to +185°F)
- Function: Power Supply for DC Loads, Switching & Monitoring of TURCK Interface Modules
- Protection: [/b]IP20
- Class 1 Div 2
- IM: Interface Module
- 1: Isolation Switch Relay
- 4: Number of Inputs
- 5: Number of Non-Hazardous Area Outputs, Reflecting Hazardous Area Input Status
- 1: Number of Additional Non-Hazardous Area Alarm Outputs
- EX: Intrinsically Safe Associated Apparatus
- T: Transistor Switch
- ATEX, IECEx
- Zone 2
- SIL 2
- Input circuits monitored for wire-break and short-circuit
- Parametrized via PC
- Complete galvanic isolation
- Removable screw terminals
- Connection Variant: Power rail with collective fault signal
- Protection Class: IP20
- Nominal voltage: 24 VDC / 7A
- Operating voltage: 11…30 VDC
- IM: Interface Module
- 1: Isolation Switch Relay
- 2: Number of Inputs
- 3: Number of Non-Hazardous Area Outputs, Reflecting Hazardous Area Input Status
- 1: Number of Additional Non-Hazardous Area Alarm Outputs
- EX: Intrinsically Safe Associated Apparatus
- R: Relay Switch
- IM: Interface Module
- 1: Isolation Switch Relay
- 2: Number of Inputs
- 2: Number of Non-Hazardous Area Outputs, Reflecting Hazardous Area Input Status
- EX: Intrinsically Safe Associated Apparatus
- R: Relay Switch
- 24VDC: Supply Voltage (19-29 VDC)
- Input: 1 Channel 4-20mA or 2-10VDC
- Output: 3(x) Relay Circuits, Digital
- Electrical Connection: 4 x 5-pole removable terminal block screw connection
- Housing: Polycarbonate/ABS
- Temperature Ranges:
- Operating: -25°C to +70°C (-13°F to +158°F)
- Storage: -40°C to +80°C (-40°F to +176°F)
- Operating Voltage: 20-250 VDC
- Function: Limit Value Indicator, 1 Input, 3 Limit Values
- Adjustment: limit value relay via TEACH button, signal flow via front switches
- Protection: [/b]IP20
- Intrinsically Safe
Specifications
Brand
Accuracy
- ≤ 0.1 % of FSO
- ≤ 0.2 % of FSO
Alarm
- None
- Non-Hazardous Area Alarm Switch
Ambient Temperature Range
- -25° to 70° C (-13° to 158° F)
Approvals & Certifications
- CSA
- FM
Circuit Protection
- Short Circuit Current 8.2 mA
Electrical Connectors
- 4 x 3-Pole Removable Terminal Blocks, Reverse Polarity Protected, Screw Connection
Enclosure, Body Material
- Polycarbonate/ABS
Environmental Protection
- IP20
Frequency
- 40 to 70 Hz
Indication
- LED Indicators for Readiness, Switching, & Error
Input
- One Channel
- Two Channel
- Four Channel
Mounting
- DIN Rail Mounting
- Panel Mount
Output
- 20-125 Vdc
- 20-250 Vac
- 4-20 mA
Output Format
- Configurable Limit Value Relay Output
- Current Output
- Relay Output
- Software Configurable
- Transistor Output
- Voltage Output
Storage Temperature
- -40° to 80° C (-40° to 176° F)
Supply Voltage
- 19-29 Vdc
- 24 Vdc
Switch Type
- SPST
Documentation
Catalogs
Certifications & Approvals
- Certifications & Approvals - Turck IM1 FM Canadian Aug 2011 pdf 73 KB
- Certifications & Approvals - Turck IM33,34,35 AltSupply FM Canadian Sep 2005 pdf 76 KB
- Certifications & Approvals - Turck IM33,34,35 AltSupply FM Mar 2012 pdf 210 KB
- Certifications & Approvals - Turck IM33,34,35 FM Canadian Mar 2007 pdf 250 KB
- Certifications & Approvals - Turck IM33,34,35 FM Mar 2012 pdf 154 KB
- Certifications & Approvals - Turck IM72 FM Canadian Jul 2006 pdf 90 KB